为了确定基于弹性分组环(resilientpacketring,RPR)的变电站通信系统实时性是否满足IEC61850标准的要求,使用网络演算理论推导出各种业务在采用双缓存媒体控制(mediumaccesscontrol,MAC)策略的弹性分组环中传输时延上界的计算方法,并以典型变电站为例,计算得到了变电站内各种数据流的传输时延上界。计算结果为:使用吉比特弹性分组环作为过程总线,当网络负载率小于80%且节点数达到上限时,实时业务的传输时延上界小于2.5ms;使用吉比特弹性分组环既作为变电站总线又作为过程总线,当最大报文长度和网络节点数达到上限时,实时业务的传输时延上界为3.5ms左右。网络演算和OPNET仿真结果表明:基于弹性分组环的变电站通信系统能够满足IEC61850标准的要求。
In order to confirm whether the real-time performance of substation communication network based on resilient packet ring (RPR) can meet the requirement of IEC 61850, a delay supremum calculus method of various services inside RPR with dual transit queue media access control (MAC) was derived, based on network calculus. A typical substation case was calculated using this method. When RPR is used as process bus, delay supremum of real-time service in RPR network with maximum nodes is below 2.5 ms if the load-rate is below 80%. When RPR is applied as both process bus and substation bus, delay supremum of real-time service in RPR with maximum nodes is about 3.5 ms if the largest packet length reached the upper limit. The calculus and OPNET simulation results indicate that the real-time performance of the substation network based on RPR can meet the real-time application requirement of IEC 61850.