Fire resistance performance of glulam beam
  • ISSN号:1003-3033
  • 期刊名称:《中国安全科学学报》
  • 时间:0
  • 分类:TU352.5[建筑科学—结构工程] TU366.3[建筑科学—结构工程]
  • 作者机构:Institute of Disaster Prevention Science and Safety Technology, Central South University
  • 相关基金:Projects(51576212,51534008)supported by the National Natural Science Foundation of China;Project(2016YFC0802501)supported by the National Key Research and Development Program of China;Project(KFKT2014ZD02)supported by the Open Fund of Key Laboratory of Building Fire Protection Engineering and Technology of Ministry of Public Security,China
中文摘要:

A glulam beam with the size of 4700 mm×300 mm×480 mm(L×W×H) was tested in the furnace to investigate the fire resistance performance of glulam beam according to the temperature curve of ISO834. Three surfaces, the bottom and the two flanks, of the glulam beam were exposed to fire in the test. Simply supported bearings were used to support the beam on which the load of 0.76 kN/m was uniformly set. The experimental results show that: 1) Sectional dimension of glulam beam was greatly diminished due to the serious decomposition and carbonization of the timber. 2) The largest vertical deformation is relatively small and it has not exceeded 3.95 mm until the end of experiment. The maximum temperature on the top surface of the glulam beam attains 180 ℃ at 3437 s, which indicates that the beam have failed according to the European standard of fire resistance tests. 3) The right end of the beam with 16 connecting holes(the connecting holes were used for the connection between bolt and column) and the slit in the beam both burnt intensely and carbonized seriously because the fire could reach the holes and slit of beam facilitating the burning.

英文摘要:

A glulam beam with the size of 4700 mmx300 mmx480 mm (LxWxH) was tested in the furnace to investigate the fire resistance performance of glulam beam according to the temperature curve of ISO834. Three surfaces, the bottom and the two flanks, of the glulam beam were exposed to fire in the test. Simply supported bearings were used to support the beam on which the load of 0.76 kN/m was uniformly set. The experimental results show that: 1) Sectional dimension of glulam beam was greatly diminished due to the serious decomposition and carbonization of the timber. 2) The largest vertical deformation is relatively small and it has not exceeded 3.95 mm until the end of experiment. The maximum temperature on the top surface of the glulam beam attains 180 A degrees C at 3437 s, which indicates that the beam have failed according to the European standard of fire resistance tests. 3) The right end of the beam with 16 connecting holes (the connecting holes were used for the connection between bolt and column) and the slit in the beam both burnt intensely and carbonized seriously because the fire could reach the holes and slit of beam facilitating the burning.

同期刊论文项目
期刊论文 66
同项目期刊论文
期刊信息
  • 《中国安全科学学报》
  • 北大核心期刊(2011版)
  • 主管单位:中国科学技术协会
  • 主办单位:中国职业安全健康协会
  • 主编:徐德蜀
  • 地址:北京市东城区和平里九区甲4号安信大厦A306室
  • 邮编:100013
  • 邮箱:csstlp@263.net
  • 电话:010-64464782
  • 国际标准刊号:ISSN:1003-3033
  • 国内统一刊号:ISSN:11-2865/X
  • 邮发代号:
  • 获奖情况:
  • 中国科技论文统计用刊,第一届中国科协期刊优秀学术论文奖
  • 国内外数据库收录:
  • 美国化学文摘(网络版),波兰哥白尼索引,美国剑桥科学文摘,中国中国科技核心期刊,中国北大核心期刊(2008版),中国北大核心期刊(2011版),中国北大核心期刊(2014版)
  • 被引量:31001